Brand:EMERSON
Product ID:KJ4110X1-BC1
Place of Origin:The United States
Warranty: 365 days
Goods status: new/used
Mail: 3598571032@qq.com
Phone/Wechat/Whatsapp:+86 15339539190
product description
Product details
The KJ4110X1-BC1 is an 8-channel analog input card designed for industrial automation that supports 4-20mA current signals and is compatible with the HART communication protocol. The card is designed for use in hazardous environments and is explosion-proof certified for use in areas with potential explosion hazards.
Main specification
Signal type: 8-channel 4-20mA input
Communication protocol: HART
Explosion-proof class: II 3 G Ex nA [ic] IIC Gc and II 3 G Ex nA [nL] IIC Gc
ATEX/IECEx certification: FM13ATEX0034U and IECEx FMG 13.0015U
Power supply specification
Local bus power supply: Not applicable
Bus field power supply: 12 VDC at 150 mA or 24 VDC at 300 mA
Field circuit power supply: 24 VDC at 30 mA/Ch.
Environmental specification
Ambient temperature: -40 °C to +70 °C
Shock: 10 g half sine wave, lasting 11 ms
Vibration: 2 to 13.2 Hz, peak-to-peak value 1 mm; 13.2 to 150 Hz, 0.7 g
Air pollutant: Compliant with ISA-S71.04-1985 Air Pollutant Class G3
Relative humidity: 5 to 95% without condensation
Installation and operation
Note: Specific instructions must be followed when installing, removing and operating this product in hazardous areas. Refer to document 12P2046 "DeltaV TM Scalable Process System Area 2 Installation Instructions" and other related installation manuals.
Remove and insert
Power disconnection: Before disassembling or connecting the device, the field power supply to the device must be disconnected, either through the field terminal or through the bus field power provided by the carrier.
Loop evaluation: I/O loop evaluation must be completed on all energy-constrained nodes.
System power supply: This unit can only be removed or inserted when the system power supply is not powered on.
Rotary keying system: To ensure compatibility between the I/O card and the block after installation, the block must have the appropriate key for the I/O card used.
Maintenance and adjustment
User not repairable: There are no user repairable parts in this unit and it cannot be disassembled for any reason.
Calibration: No calibration required.
Note: Please refer to the product label for serial number, manufacturing location and manufacturing date.
Warning: Specific instructions for the installation, removal and operation of this product in hazardous areas must be followed.
Product Parameter
Model Number: KJ4110X1-BC1
Origin:USA
EMERSON series of products
MVME6100 | PR9268/303-000 |
VE3008 | A6120 9199-00002 |
MVME5500 | A6500-UM |
A6220 9199-00009 | A6500-CC 9199-00120 |
A6210 9199-00003 | PR6426/000-010+CON021 |
A6110 9199-00001 | 1X00416H01 |
+86 15339539190