Brand:EMERSON
Product ID:SE4302T02
Place of Origin:The United States
Warranty: 365 days
Goods status: new/used
Mail: 3598571032@qq.com
Phone/Wechat/Whatsapp:+86 15339539190
product description
Product details
The SE4302T02 is an analog output characteristic module (CHARM) that supports 4-20 mA current output with or without the HART protocol. The module is designed for industrial automation systems for precise control and monitoring of analog signals.
Specification parameter
Sensor type:
Supports 4 to 20 mA output with or without HART protocol
Supports 0 to 20 mA output (option)
Nominal signal range (span) :
4 to 20 mA
(0 to 20 mA optional)
Full signal range:
0 to 24 mA
Accuracy in temperature range:
0.25% span (0 to 60°C)
0.5% span (-40 to 70°C)
Resolution:
16-bit D/A converter
Calibrate:
No calibration required
Available on-site power supply:
20 mA @ 15 V DC power supply to 750 Ω load
Field circuit protection:
24 mA current limiting circuit
Field wiring disconnection
CHARM Power Requirements:
Max. 42 mA @ 24 V DC
CHARM heat dissipation:
0.48W
HART supports:
HART v7 transparent transmission with AMS support
Provide HART v7 variables and device status information to the control system
HART data update rate:
Update rates are faster than once per second, depending on HART communication load and device type
Product characteristics
With high precision, high resolution and reliable output performance, the SE4304T01 module can meet the needs of analog signal control in the field of industrial automation. Its built-in HART communication function enables the module to communicate with smart sensors for remote monitoring and configuration. In addition, the modules are designed with field circuit protection and heat dissipation to ensure stable operation in harsh industrial environments.
Application field
The module is widely used in industrial automation control system, such as process control, production line monitoring, environmental monitoring and other fields. Through the connection with sensors and actuators, the precise measurement and control of analog signals such as temperature, pressure and flow rate are realized.
Installation and maintenance
Follow the installation instructions in the product manual and ensure that the module is properly connected to the power supply and load. During maintenance, disconnect the power supply and follow the safety regulations.
Matters needing attention
Please ensure that the working temperature of the module is within the specified range.
Avoid using modules in environments with damp, corrosive gases or strong electromagnetic interference.
If you need to replace a module, make sure to use a replacement of the same model as the original module.
Sum up
SE4302T02 is a powerful and stable analog output characteristic module for analog signal control and monitoring in industrial automation control systems. Through its high-precision output and reliable communication functions, users can achieve accurate process control and data acquisition, improving production efficiency and system stability.
Product Parameter
Model Number: SE4302T02
Origin:USA
EMERSON series of products
MVME6100 | PR9268/303-000 |
VE3008 | A6120 9199-00002 |
MVME5500 | A6500-UM |
A6220 9199-00009 | A6500-CC 9199-00120 |
A6210 9199-00003 | PR6426/000-010+CON021 |
A6110 9199-00001 | 1X00416H01 |